Surge Protection Device OBV1-C40 (3+NPE)
    >> Power-Surge-Protection
Surge Protection Device OBV1-C40 (3+NPE) In:20kA Imax:40kA
     
 
Advantage >>

Surge Protection, Lightning Protection, Surge Protection Device, Surge Suppressor, Surge Arrester, Surge Protective Device, Surge Protector, Lightning Solution, China Surge Protection Device Manufacturer, China Surge Arrester Supplier

Products Details >>
 
Product Description
OBV1-C40 series surge protection device (in short: SPD, alias: surge suppression, surge arrester) is suitable for TN-S, TN-C-S, TT, IT etc. power supply system of AC 50/60Hz, <440V, installed on the joint of LPZ1 or LPZ2 and LPZ3, it’s designed according to IEC61643.1, GB18802.1, it adopts 35mm standard rail, there is a failure release mounted on the module of surge protection device. When the SPD fails in breakdown for over-heat and over-current, the failure release will help electric equipments separate from the power supply system and give the indication signal, green means normal, red means abnormal, it’s also could be replaced for the module when has operating voltage.
 
Product Features
1. Inside over-current and over-heat protection, temperature control open circuit.
2. Module design, convenient installation, could be replaced online.
3. Smallness leak current, response quickly, less residual voltage.
4. Signal indication device, green(normal), red(abnormal).
5. New technology, highly energy, clearance discharge pole(NPE).
 
Model and Meaning
 
Main Technical Parameters
 
OBV1-C40
NPE
Max. Continuous Operating Voltage Uc (V~)
275V
320V
385V
440V
275V / 320V
Voltage Protection Level Up (V~) kV
1.2kV
1.5 kV
1.8 kV
2.0 kV
1.5kV
Nominal Discharge Current In (8/20µs) kA
20kA
Iimp(10/350): 12.5 kA
Max. Discharge Current Imax (8/20µs) kA
40kA
Response Time ns
<25ns
Test Standard
IEC61643-1, GB18802
The Cross Section of L/N Line (mm2)
25-35 mm2
The Cross Section of PE Line (mm2)
25-35 mm2
Fuse or Switch (A)
25A~32A
Operating Environment (centidegree)
-40~+85
Relative Humidity (25 centidegree)
<95%
Installation
Standard Rail 35mm
Material of Outer Covering
Fiberglass PC
 
Dimension
 
 